Security of control systems in wind and solar farms

A renewable energy farm is an unmanned facility, and therefore remotely controlled by design. The remote access gateway is not a convenience but a precondition of operation. It is also the shortest path into the site. We provide independent supervision of that layer, both during construction and at farms already generating.

Who this is for

For investors, SPVs, funds and general contractors delivering solar and wind farms: sites under construction, sites before commissioning, and farms already in production, including whole portfolios built to a repeating template. Our supervision also covers connected battery storage and the substation, in the control layer.

What the farm's IT and OT layer is made of

A typical farm today consists of several independently delivered layers. Each is supplied by a different party, on a different schedule and to its own habits. All of them ultimately land in one network in one substation.

Inverters and turbine controllers

PV inverters or wind turbine controllers together with the production management and power regulation system.

Substation controllers and telecontrol

Substation controllers, RTU telecontrol units and bay protection relays.

SCADA and HMI operator stations

The supervisory system and operator workstations, including those shared with the O&M service provider.

Serial servers and converters

Simple devices mediating serial communication, through which controllers talk to the rest of the site.

Link to the grid operator

The connection to the distribution or transmission operator, with the telemetry it requires.

Remote access channels

The investor's VPN gateway, the contractor's service channel, the inverter or turbine manufacturer's channel, and device connections to the manufacturer's cloud.

Auxiliary systems

CCTV, access control, weather stations, tracker control, battery storage, uninterruptible power supply.

Every contractor is responsible for their own system, but nobody is responsible for how those systems look together — or for what can be done by reaching them from outside.

What has already happened

The events below are documented and publicly described. We cite them not to alarm, but because each shows a different, concrete mechanism, and each concerns a facility of the kind you are building or operating.

Poland, 29 December 2025

How it looked from the inside

In the course of a single day an attacker carried out destructive actions at no fewer than thirty Polish wind and solar farms and at a manufacturing company. The CERT Polska (NASK) report describes the character of those actions unambiguously: they were purely destructive, with no ransom demand and no theft for resale. The entry route was the same everywhere — an edge device acting as firewall and VPN concentrator, reachable from the whole internet and requiring no second authentication factor. Substation controllers held factory credentials, bay protection relays had an FTP service enabled by default, and operator stations used the default local administrator password set during deployment.

Same day, different outcome

The site that held

A combined heat and power plant attacked the same day had been penetrated more deeply than the farms: the attacker had been inside its network since spring 2025 and had exfiltrated the central account and password database. Lasting damage was nevertheless not done. Modern endpoint protection recognised the destructive process and blocked it on every machine at once. The difference between a site disabled and a site defended was not luck — it followed from decisions taken earlier, when the environment was being built and configured.

Germany, 2022

Three events in six weeks

On 24 February 2022 an attack on a satellite network disabled modems across Europe. A turbine manufacturer lost remote supervision of more than 5,800 wind turbines totalling roughly 11 GW — the turbines kept running in automatic mode, but for weeks there was no way to monitor or remotely regulate them. On 31 March a major turbine manufacturer detected an intrusion and pre-emptively shut down IT systems at many locations. Overnight on 11–12 April a service company operating wind farms suffered a targeted attack and within two days cut remote connections to some two thousand turbines.

United States, March 2019

An unpatched firewall and 500 MW without supervision

A renewable asset operator lost SCADA visibility over roughly 500 MW of wind and solar capacity across three states. There was no intrusion: the attacker exploited a known vulnerability in the web interface of network firewalls, causing them to reboot repeatedly. The official analysis identified a single cause — the vendor patch was available but had not been applied, because nobody was supervising the software currency of edge devices. This is the cheapest avoidable incident in the whole set, and also the most common.

Inverters and monitoring

Vulnerabilities are the rule, not the exception

In 2023 it emerged in Japan that around 800 devices monitoring photovoltaic installations from a single manufacturer had been taken over and used by criminals for their own purposes. In March 2025 a research team published an analysis of the photovoltaic systems of three large inverter manufacturers, describing 46 vulnerabilities — from hard-coded passwords, through takeover of the manufacturer's cloud account, to unauthenticated firmware update over the air. An inverter and a monitoring device are network-connected computers and demand the same discipline as a server.

The manufacturer's channel

A risk that requires no attacker

In November 2024 some inverters from one manufacturer were remotely disabled in several countries — not through an attack, but as a consequence of a distribution dispute between the manufacturer and its commercial partner. In May 2025 industry reports described the discovery, in some inverters and battery systems, of undocumented communication modules creating a channel alongside the one protected by the site firewall. Since 2025 Lithuania has restricted remote access to installations above 100 kW for entities from states deemed a security threat, and in April 2026 the European Commission restricted funding for projects using inverters from suppliers considered high risk.

All the events cited come from publicly available sources: CERT Polska (NASK) reports, company statements and annual reports, regulatory decisions, security researchers' publications and press coverage. This material is informational and does not constitute legal advice.

How a farm differs from other assets of similar value

The risk profile of a renewable farm does not come from it being an unusually attractive target. It comes from several structural features that together form a profile rarely found elsewhere.

No permanent human presence

There is nobody to raise the alarm and nobody to notice that something is wrong. Everything known about the site arrives over the very link an attacker may control.

Repetition across the portfolio

Farms are built in series, by the same contractors, to the same configuration template. One flaw in the template is a flaw in every site, and one password is often the password to the whole portfolio.

Long-lived hardware, short-lived support

A farm is meant to run for 25 to 30 years. Controllers, relays and inverters have far shorter vendor support. The update and replacement plan for the full life cycle is a decision made at purchase, not ten years later.

Revenue depends directly on continuity

Every day without generation is revenue lost for good, and with disabled automation we are talking about rebuilding the configuration of the systems, not about a simple restart.

Connection to the power system

This creates obligations towards the grid operator and requires the connection to be separated from the rest of the site, in both directions.

Responsibility for the supply chain

A farm's security is in practice the sum of decisions made by several suppliers, over which the investor has influence only at the contract and acceptance stage.

What exactly we verify

For each area we agree with the investor what precisely counts as "verified", so that the scope is unambiguous for all parties.

Remote access and edge devices

What we verify

What is visible from the internet and why; restriction of connection sources, a second authentication factor without exceptions, software currency of the firewall and VPN concentrator.

Risk if skipped

The shortest path into the site — precisely the one used on 29 December.

Network segmentation

What we verify

Whether the control, monitoring, office and auxiliary layers are genuinely separated rather than merely described in the design; whether everything is visible from the remote access gateway.

Risk if skipped

One compromised device grants access to the entire site.

Accounts and passwords in the control layer

What we verify

Elimination of factory credentials on controllers, relays, HMI stations and network devices; named accounts, role-appropriate privileges, no shared passwords between sites.

Risk if skipped

The single most common cause of incidents across the sector.

Inverters, turbines and vendor channels

What we verify

The scope and manner of device connections to manufacturer systems, presence of external connectivity (cloud, dongle, modem), the ability to change settings remotely and its limitation in the contract.

Risk if skipped

An uncontrolled control channel bypassing the site's protections.

SCADA, HMI and operator stations

What we verify

Configuration of the supervisory system and workstations, O&M service provider access, operating system currency, remote desktop and how it is secured.

Risk if skipped

Takeover of site control from a position where it looks like normal operator activity.

Endpoint and server protection

What we verify

The presence and actual operation of modern protection that detects destructive activity, not merely classic antivirus.

Risk if skipped

Nothing to stop an attack in progress — this is the layer that saved the CHP plant.

Connection to the grid operator

What we verify

Separation of the telemetry link from the site's other systems and control over what passes through it in both directions.

Risk if skipped

Risk of the farm being used as a route towards the operator's infrastructure.

Software currency and hardware life cycle

What we verify

The state of device software at acceptance, the update plan for coming years, and the vendor support horizon against a 25 to 30 year asset life.

Risk if skipped

A site commissioned with vulnerabilities publicly known for years and no plan for the years ahead.

Backups and recoverability

What we verify

Not only whether backups of device and system configurations are taken, but whether they can actually be restored and whether they survive a destructive attack.

Risk if skipped

No way back; rebuilding from zero with contractors involved and waiting for parts.

Event logging and detection

What we verify

Whether systems record who did what, whether logs are collected off site, and whether anyone acts on them.

Risk if skipped

An intruder present for months undetected, as in the incidents described.

Contractor and service provider access

What we verify

Who retains remote entry to the systems after work ends, on what terms and for how long; credential rotation after every change of contractor.

Risk if skipped

Persistent, uncontrolled access by third parties, often long after the contract has ended.

Documentation and procedures

What we verify

Whether a current description of what is connected and how exists, along with an incident response procedure including mandatory notification.

Risk if skipped

Reacting by trial and error at the worst possible moment.

How we structure the engagement

We agree the commercial terms up front — a fixed fee per stage or per site, or a monthly engagement for the duration of construction. In every variant, support with implementing our recommendations is included in the agreed fee.

Full supervision, from design to commissioning

When it makes sense

A site at design stage or in early delivery

What it covers

All five stages of Track A, support with implementing recommendations, retest and handover of documentation

Supervision from systems commissioning

When it makes sense

Construction well advanced, automation and SCADA only now arriving on site

What it covers

Stages 3 to 5: ongoing configuration control, pre-commissioning testing, report and retest

Review of an operating site

When it makes sense

The farm is already generating and the state of the control layer is not fully known

What it covers

Inventory, condition assessment, remediation plan matched to service windows, and verification of completion

Portfolio variant

When it makes sense

Several or a dozen sites built to the same template

What it covers

Detailed examination of the first site, a checklist for the remainder, a common standard for the portfolio

Frequently asked questions

Wind and solar farms — the questions investors ask.

Yes, and it has already happened in Poland. On 29 December 2025 substation controllers were disabled at no fewer than thirty Polish wind and solar farms. The CERT Polska report shows that no advanced technique was used: a remote access gateway visible from the internet without a second authentication factor, plus factory passwords on the devices inside, was enough. A farm is an attractive target precisely because it is unmanned, so there is nobody to notice that something is happening.

Because the question is not about competence but about roles in the project. The contractor delivers their own scope under schedule and budget pressure, and it is not their job to check how their system interacts with the others, or whether the service conveniences they leave behind create risk for the whole. The O&M provider is accountable for availability, and remote access is their working tool. We sell neither hardware nor deployments, so we have no interest in staying quiet about anything.

Yes, only the order of work changes. At an operating site we begin by establishing the facts, because in practice nobody knows them in full: a complete list of devices, software versions, accounts, remote access channels and external connections, including the ones everyone has forgotten. This is usually the most surprising part of the whole exercise. A remediation plan then follows, split into changes that can be made remotely, those requiring a site visit, and those requiring an outage.

No. The entire physical and electrical layer stays outside our scope: modules, mounting structures, turbines and their mechanical parts, DC and AC cabling, cable routes, transformers, switchgear, switching apparatus, construction and installation works, measurements, testing and trade acceptance. We assume that this work is performed correctly and is subject to its own appropriate trade supervision. Our role begins exactly where the installer's ends: the device is mounted and connected, and now somebody is configuring it.

The amendment to the national cybersecurity system act implementing the NIS2 directive entered into force on 3 April 2026, and electricity generation falls within the regulated sectors. The status of a particular SPV is not always obvious, because the size criterion may or may not be met depending on the group structure, and the final classification is worth confirming with legal counsel. From our perspective something else matters: the grid operator, the financing bank and the insurer increasingly ask the same questions regardless of statutory status.

The investor receives a catalogue of security requirements for contractors, an inventory of the site's logical layer, a register of non-conformities with the history of their resolution, verification test reports, a final report with an acceptance recommendation, and a retest once findings are closed. Implementing the recommendations is included in the supervision fee: we sit down with the contractor's or O&M engineer at the specific device and work through the configuration with them. We do not leave the investor holding a list of findings to enforce alone.

The full study

The full study for wind and solar farms

Fourteen pages: documented incidents in the renewable sector with their sources, the complete table of areas under control, how the supervision runs on both tracks, NIS2 requirements, and the engagement variants with commercial terms.

Farma bez obsługi, ale nie bez dostępu

PDF document. The study is available in Polish. We use your details solely to respond to this enquiry.

Before you accept the farm's systems

We propose a working meeting with the people responsible for the project or for operations. We will go through the list of systems planned for the site, or already working in it, and agree which of them should fall under supervision and what "verified" means for each.